T501 HART -> PROFIbus DP

Gateway for allowing HART instruments to connect to PROFIbus DP network

General description:

The T501 is DIN rail module for interfacing up to four HART instruments to a PROFIbus DP network.  Both current
sinking and current sourcing HART transmitters are supported.

The HART instruments must be preconfigured to multidrop and be given addresses in the range 1 - 16. The T501 will automatically establish connection to the HART transmitter at power-up. When the HART instrument is detected, key parameters are read from the instrument and will be visible on the PROFIbus side. The T501 will read Unit codes, sensor limits and range values from the HART transmitters. These values will be available on PROFIbus from a Master Class two using DP V1.

No configuration is required.

T501 supports the DP V1 protocol and PA Profile 3.0. 

T501 includes a HART master  in order to communicate with a HART instrument. The module reads the variables from the instrument and converts this to a dynamic variable on DP. Four AI Function Blocks are supported, one for each instrument. Other Function blocks can be added on request. The HART slaves are supposed to work in multidrop mode

The HART Universal command parameters are available from the DP side.

By reconfiguring the T501 it is possible to read four dynamic variables from one instrument. The latter application will 
require use of a configuration tool or the T501 can be ordered preconfigured from FINT.

The HART instrument may be powered through the T501. T501 has a separate 24 V input for this.

The HART support is limited to the Universal commands. The T501 does not support configuration of the HART transmitter through PROFIbus.

The T501generates one measured variable including a status variable indicating the quality of the
measurement for each HART transmitter. The Primary Variable (PV) will be continuously read and updated. Any HART communication problem will be reported in the PROFIbus Diagnostics message.

The T501supports alarm flagging. The user can configure four alarm levels using a standard configuration tool.

The T501supports low-pass filtering. The user can configure the damping value using a standard configuration tool.


Applications:

The T501 is intended for integration of existing HART instruments into PROFIbus DP network. It is intended for system integrators that are building PROFIbus based systems, and manufacturers of measurement devices who want to offer PROFIbus DP capabilities on their HART instruments.